NHXH, NHXCH FE 180/E90

Fire resistant cable with orange sheath, halogen-free

NHXH-J FE180/E90

Cable structure

  • Bare copper conductor, solid or stranded according to DIN VDE 0295 IEC 60228 cl. 1 or 2
  • Double core insulation of mica tape and cross-linked polymer compound
  • Cores color coded according to DIN VDE 0293-308, green-yellow earth core (from 3 cores above)
  • Cores stranded in layers and wrapped with glass-fibre tape as flame-protection
  • For version (N)HXCH concentric conductor of copper tape and copper wires
  • Orange sheath of halogen-free polymer compound according to DIN VDE 0207 part 24, flame retardant

Technical data

  • Halogen-free, flame-resistant cable according to DIN VDE 0266, orange
  • Insulation integrity under the impact of flames 180 min according to IEC 60331, DIN VDE 0472 part 814
  • Function integrity according to DIN VDE 4102 part 12 E90
  • Temperature range flexing from -40°C to +70°C; max. permitted temperature at conductor +90°C
  • Nominal voltage Uo/U 0,6/1 kV
  • Test voltage a.c.4000 V
  • Minimum bending radius approx. 15 x cable diameter

Tests

  • Flame-retardant to DIN VDE 0482-266-2-4/EN 60332-2-24/IEC 60332-3-24 (cat.C)
  • Low corrosiveness of combustion gases to IEC 60754-2
  • Halogen-free to IEC 60754-1
  • Smoke density to IEC 61034-1,61034-2
  • Insulation integrity under direct flame propagation according to DIN VDE 0472 part 814, IEC 60331
  • Function integrity according to DIN VDE 4102 part 12 of electrical cable system for a period of 90 min.

Color codes of NHXCH

  • 2-core cable: blue/brown
  • 3-core cable: brown/black/grey
  • 4-core cable: blue/brown/black/grey
  • from 7 cores above, black cores with white numbering

Application

These flame-resistant cables are used for all locations where a special protection against fire and fire damage to human life and equipment is necessary such as in industry complexes, power stations, public buildings, hotels, airports, subways, theatres, hospitals etc. These cables are suitable for fixed installation in dry or wet areas but not suitable as a direct burrial into water or earth. For installation in conduits all precautions must be taken to prevent an accumulation of water in the pipes.

FE180: Insulation integrity for 180 min. Test according to IEC 60331 and DIN VDE 0472 part 814 Insulation integrity under direct impact of flames for a period of 180 minutes
E90: Function integrity according to DIN VDE 4102 part 12 of electrical cable system for a period of min. 90 minutes assures the functional performance of water-pressure rising systems to avoid smoke and heat in safety stairs, machine rooms, emergency lifts, extract systems etc.

Note:

  • CE = the product is conformed with the EC Low-Voltage Directive 2014/35/EU.
  • Conforms to RoHS.

Technical characteristics

NHXH FE180/E90

Ordering code Number of cores × core cross-section[mm2] Approx. outer ø [mm] Copper weight [kg/km] Approx. cable weight [kg/km]
0553000 3 × 1,5 re 15,0 43 350
0553001 3 × 2,5 re 16,0 72 390
0553002 3 × 4 re 17,0 115 475
0553003 3 × 6 re 18,5 173 560
0553004 3 × 10 re 19,5 288 720
0553005 3 × 16 rm 22,0 461 970
0552990 3 × 25 rm 26,0 720 1400
0552991 3 × 35 rm 29,0 1008 1770
0552992 3 × 35+16 rm 29,5 1162 1930
0552993 3 × 50+25 rm 33,5 1680 2610
0552994 3 × 70+35 rm 38,0 2352 3470
0552995 3 × 95+50 rm 43,0 3216 4670
0552996 3 × 120+70 rm 47,0 4128 5810
0552997 3 × 150+70 rm 51,0 4992 6840
0552998 3 × 185+95 rm 57,0 6240 8600
0552999 3 × 240+120 rm 62,5 8064 10900
0553006 4 × 1,5 re 16,0 58 380
0553007 4 × 2,5 re 18,0 96 465
0553008 4 × 4 re 19,0 154 560
0553009 4 × 6 re 20,0 230 650
0553010 4 × 10 re 22,0 384 880
0553011 4 × 16 rm 24,0 614 1190
0553012 4 × 25 rm 28,0 960 1730
0555013 4 × 35 rm 31,0 1344 2200
0553014 4 × 50 rm 35,0 1920 2890
0553030 4 × 70 rm 40,0 2688 3920
0553031 4 × 95 rm 45,0 3648 5210
0553070 4 × 120 rm 49,0 4608 6370
0553071 4 × 150 rm 54,0 5760 8070
0553072 4 × 185 rm 59,0 7104 9970
0553073 4 × 240 rm 66,0 9216 12830
0553015 5 × 1,5 re 18,0 72 475
0553016 5 × 2,5 re 19,0 120 500
0553017 5 × 4 re 20,0 192 600
0553018 5 × 6 re 21,0 288 710
0553019 5 × 10 re 24,0 480 930
0553020 5 × 16 rm 26,0 768 1430
0553021 5 × 25 rm 30,0 1200 1910
0553028 5 × 35 rm 34,0 1680 2800
0553029 5 × 50 rm 39,0 2500 3730
0553022 7 × 1,5 re 19,0 101 560
0553027 7 × 2,5 re 21,0 168 750
0553025 10 × 1,5 re 23,0 144 750
0553026 10 × 2,5 re 24,8 240 900
0553023 12 × 1,5 re 25,0 173 850
0553024 12 × 2,5 re 26,1 288 990

NHXCH FE180/E90

Ordering code Number of cores × core cross-section[mm2] Approx. outer ø [mm] Copper weight [kg/km] Approx. cable weight [kg/km]
0553032 3 × 1,5/1,5 re 16,9 66 370
0553033 3 × 2,5/2,5 re 18,0 104 430
0553034 3 × 4/4 re 19,0 161 530
0553035 3 × 6/6 re 20,1 240 640
0553036 3 × 10/10 re 21,8 408 850
0553037 3 × 16/16 rm 24,5 643 1130
0553038 3 × 25/16 rm 29,0 874 1550
0553039 3 × 35/16 rm 30,0 1162 2000
0553040 3 × 50/25 rm 33,0 1680 2600
0553041 3 × 70/35 rm 37,0 2352 3480
0553042 3 × 95/50 rm 43,0 3216 4680
0553043 3 × 120/70 rm 47,0 4128 5800
0553044 3 × 150/70 rm 52,0 4992 6850
0553045 3 × 185/95 rm 57,0 6240 8600
0553046 3 × 240/120 rm 63,0 8064 10980
0553047 4 × 1,5/1,5 re 18,0 81 430
0553048 4 × 2,5/2,5 re 18,9 128 500
0553049 4 × 4/4 re 20,1 200 600
0553050 4 × 6/6 re 21,2 297 730
0553051 4 × 10/10 re 23,0 504 1060
0553052 4 × 16/16 im 25,2 796 1360
0553053 4 × 25/16 rm 30,0 1142 1900
0553054 4 × 35/16 rm 33,5 1526 2410
0553055 4 × 50/25 rm 38,0 2203 3180
0553056 4 × 70/35 rm 42,5 3082 4385
0553057 4 × 95/50 rm 47,5 4208 5800
0553058 4 × 120/70 rm 51,5 5388 7225
0553059 4 × 150/70 rm 57,0 6540 8710
0553060 4 × 185/95 rm 63,5 8159 10700
0553061 4 × 240/120 rm 71,0 10546 13935
0553062 7 × 1 5/2,5 re 20,8 133 670
0553065 12 × 1,5/2,5 re 27,0 205 1050
0553064 24 × 1,5/6 re 36,5 413 1900
0553065 30 × 1,5/6 re 39,0 499 2200
0553066 7 × 2,5/2,5 re 21,2 200 680
0553067 12 × 2,5/4 re 27,0 334 1050
0553068 24 × 2,5/10 re 37,0 696 1900
0553069 30 × 2,5/10 re 39,0 840 2200

Products

Metal prices (€/100kg)

28.11.2024

Al = 354.23€/100kg
Cu = 876.31€/100kg

27.11.2024

Al = 355.62€/100kg
Cu = 879.19€/100kg

26.11.2024

Al = 359.27€/100kg
Cu = 881.54€/100kg

25.11.2024

Al = 359.44€/100kg
Cu = 879.67€/100kg

22.11.2024

Al = 355.53€/100kg
Cu = 880.82€/100kg

Top news

ISO recertification

In August 2018 our company succesfully passed recertification audit under ISO:9001 – Quality Management System

New company name

Dear business partners, I would like to inform you about change of legal status of our company DDA spol. s r.o. into DDA a.s. registered in Business regist...

New products added!

New products added to our portfolio: SERVO-FLEX-PUR-JZ - highly flexible cable for drag chains SERVO-FLEX-PVC-JZ - flexible power supply cable for s...

New website launched

DDA Ltd. has launched its new website.

ISO 9001:2000 certificate

DDA Ltd. is a holder of ISO 9001:2000 certificate.

Česky English
Developed by: FRONK Design
All rights reserved DDA © 2006